Power outage runbook for PBX and SBC
Overview
Voice is life-safety adjacent for some sites. UPS and generator tests must include SBC, core switch, PoE budget.
Runbook sections
- Detection: UPS SNMP traps, carrier portal LOS alerts.
- Priorities: 911 routes, security desk, elevator phones per legal ladder.
- Runtime: UPS minutes at current load; which voice subnets you shed first.
Testing
Semi-annual pull the plug drill on staging gear minimum; annual full site if client critical; log actual hold-up time.
Cloud dependency
Teams Phone still needs local internet and often SBC on-prem—starlink/cellular backup conversation belongs here.
Recovery
Cold-start order: core switch → SBC → DHCP / TFTP servers; validate NTP before TLS sessions freak out.
Comms template
Status page + SMS tree for “inbound calls rerouted to cell queue”—prewritten saves 20 minutes of panic prose.